We noticed an issue in this example file - the branch SHWSys1 Supply Equipment Branch has the SHWSys1 Water Heater and node connections defined, but the definition of the waterheater itself does not include the node connections. The file simulates with only a warning. The SVG shows the loop connections without the waterheater on the supply side of the loop.
I have EnergyPlus back to version 9.4 installed on this computer, and the example file shows the same pattern in that version as well.
Branch:
Branch,
SHWSys1 Supply Equipment Branch, !- Name
, !- Pressure Drop Curve Name
WaterHeater:Mixed, !- Component 1 Object Type
SHWSys1 Water Heater, !- Component 1 Name
SHWSys1 Pump-SHWSys1 Water HeaterNode, !- Component 1 Inlet Node Name
SHWSys1 Supply Equipment Outlet Node; !- Component 1 Outlet Node Name
WaterHeater
WaterHeater:Mixed,
SHWSys1 Water Heater, !- Name
0.1514, !- Tank Volume {m3}
SHWSys1 Water Heater Setpoint Temperature Schedule, !- Setpoint Temperature Schedule Name
2.0, !- Deadband Temperature Difference {deltaC}
82.2222, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
11722.84, !- Heater Maximum Capacity {W}
, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency
, !- Part Load Factor Curve Name
571, !- Off Cycle Parasitic Fuel Consumption Rate {W}
electricity, !- Off Cycle Parasitic Fuel Type
0.8, !- Off Cycle Parasitic Heat Fraction to Tank
571, !- On Cycle Parasitic Fuel Consumption Rate {W}
electricity, !- On Cycle Parasitic Fuel Type
, !- On Cycle Parasitic Heat Fraction to Tank
zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
CORE_ZN, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
1.205980747, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
1.205980747, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
4.048e-06, !- Peak Use Flow Rate {m3/s}
BLDG_SWH_SCH; !- Use Flow Rate Fraction Schedule Name
Operating System (Multiple choices)
Windows
Operating System Version
Windows 11
Version of EnergyPlus
25.1.0
Unmethours link or helpdesk ticket number
N/A
Defect file
standard example files that come with EnergyPlus